Common Faults and Solutions of Gas Boiler burners (II)

February 11,2023

No ignition, air pressure is normal, electricity has no ignition-- Gas Boiler burners

Fault phenomenonNo ignition, air pressure is normal, electricity has no ignitionTangshan Jinsha Combustion Heat Energy Co.,Ltd
ItemCause of failureExclusion measure
1The ignition transformer is burnt outrenew
2The cable is damaged or offReinstall or replace
3Too large or too small clearance, relative size of ignition rod positionreadjustment
4The electrode is broken or short-circuited to the groundReinstall or replace
5Improper spacingreadjustment

Fire for 5 seconds and then turn off the fire

Fault phenomenonFire for 5 seconds and then turn off the fireTangshan Jinsha Combustion Heat Energy Co.,Ltd
ItemCause of failureExclusion measure
1The pressure is insufficient, the pressure drop is too large, and the gas supply flow is smallAdjust the air pressure and clean the screen
2The air volume is too small, the combustion is not sufficient, and the smoke is thickReadjustment
3Too much air, white gasReadjustment